Load Bank Testing
What it means.
Load bank testing applies an artificial electrical load to a generator to verify it can produce its rated output under real working conditions, not just idle or start on command. It is the only test that confirms a standby generator will actually carry a building’s full load during an outage, and it is how a site that cannot reach 30% load with building demand meets the NFPA 110 exercise requirement.
Governing standard
NFPA 110 Section 8.4.2 specifies the supplemental annual load bank protocol (30 minutes at 50% of nameplate followed by 60 minutes at 75% in current editions) and Section 8.4.9 the 36-month run for Level 1 systems.
Related service
Hedgehog Power Systems handles this under Full Diagnostic Inspections & General Repair.
Also in the glossary.
NFPA 110 Level 1 and Level 2
NFPA 110 classifies an emergency power supply system by Level, Type, and Class. Level 1 covers systems where f...
Emergency Power Supply System (EPSS)
An emergency power supply system, or EPSS, is the complete system that delivers backup power to a building: th...
Wet Stacking
Wet stacking is the buildup of unburned fuel and carbon in a diesel generator’s exhaust system, caused by runn...
Automatic Transfer Switch (ATS)
An automatic transfer switch, or ATS, is the device that detects a utility power failure, disconnects a facili...