Breaker & Electrical System Testing

Breaker testing checks trip times, insulation resistance, contact resistance, and fault handling under simulated load. Hedgehog Power Systems runs this testing on generator switchgear and breakers across Illinois and the Midwest so your protection devices actually trip when a fault happens, not just when the panel looks fine.

Scope of work

What's included.

  • Trip-time and insulation-resistance testing
  • Contact resistance measurement
  • Simulated fault and overload testing
  • Written test report with pass/fail results per device
  • NFPA 70E trained and certified technicians
Questions

About this service.

How often does NFPA 110 require a generator to be tested?

NFPA 110 calls for a weekly inspection, a monthly exercise run of at least 30 continuous minutes at 30% or more of nameplate kW (or the manufacturer’s minimum exhaust gas temperature), monthly operation of each transfer switch, annual fuel quality testing, and, for Level 1 systems, a 4-hour run at least once every 36 months. The edition that applies is the one adopted by your local authority having jurisdiction, so confirm it with your AHJ.

How often should my generator be serviced?

Generators typically need full service annually or every 200 to 500 hours of operation, whichever comes first. We also recommend weekly visual checks and monthly exercise runs. A tailored plan can include breaker testing, fuel tank cleaning, and engine maintenance to prevent issues before they start.

What does a typical generator maintenance visit include?

A standard visit covers fluid checks (oil, coolant, fuel), filter inspections and replacements, battery testing, visual inspection for leaks or wear, control panel inspection, and system performance verification. Every visit ends with a written record of what was found and what was done.