Paralleled generator system of the kind used for hospital emergency power

Hospitals & Healthcare

Hospital generator service is a documentation job as much as a mechanical one. Hedgehog Power Systems maintains and tests emergency power systems for hospitals and healthcare facilities across Illinois and the Midwest, with testing plans built around NFPA 110 and Joint Commission EC.02.05.07 and a written record from every visit.

What drives the work

The requirements this facility answers to.

Requirements differ between editions of NFPA 110, and the edition that applies is the one adopted by your local authority having jurisdiction. Confirm the adopted edition with your AHJ, accreditor, or insurer before relying on any schedule.

01

Joint Commission EC.02.05.07

Twelve generator tests a year at intervals of 20 to 40 days, each at least 30 continuous minutes at 30% of nameplate or the manufacturer’s minimum exhaust temperature. Transfer switches tested on the same cycle. A 4-hour test at least once every 36 months.

02

NFPA 99 Type 1 essential electrical system

Hospitals are Category 1 facilities. The Life Safety and Critical branches must be back within 10 seconds, on separate transfer switches, with the Equipment branch following on a programmed delay.

03

CMS Life Safety Code survey

CMS reviews emergency power records under the 2010 edition of NFPA 110 and the 2012 edition of NFPA 99. Missing or incomplete logs are among the most common citations.

What we do here

Scope of work.

  • Testing plans that match the 20-to-40-day Joint Commission cycle
  • Transfer switch testing on the same schedule as the generator
  • Written records with date, technician, conditions found, corrective action, and post-repair results
  • Breaker exercising and fuel quality testing on the annual cycle
  • Preparation ahead of a survey, so the binder is ready before the surveyor asks
Site assessment

Start with a walk-through.

We inventory the generators and transfer switches, confirm the Level and Type, review the last twelve months of records, and hand back a written testing plan.